PLC output is on but the pump running feedback is off
Trace demand, permissive, output and feedback as separate signals in a pump simulation. Identify the first mismatch in a scan table.
PlantFlow 3D team · PLC and automation
Four signals with different jobs
A pump training panel has an automatic level demand, an overload-healthy permissive, a PLC run command and a running feedback input. The word “run” appears in more than one label. That does not make the signals interchangeable. A demand says what the process wants. A permissive says whether the modeled logic allows it. A command records a controller decision. Feedback reports the state of a separate observed point.
Read the tag before the ladder symbol
Write what a stored one means beside every tag. For OL_OK, one means the overload is healthy in this model. For RUN_FB, one can mean the contactor feedback contact has closed. A normally closed physical overload contact can feed an input that a ladder instruction examines for a true value. The physical drawing and the program describe two stages in the same chain, so matching their symbols by appearance is an unreliable shortcut.
Find the source and destination of one bit. A coil instruction writing a command bit is different from an input instruction reading feedback. If the diagram shows KM1 auxiliary feedback, the model is reporting contactor operation. It has not independently measured pump flow or proved liquid delivery.
Make a scan table
Use four columns for demand, healthy permissive, command and feedback. With demand off, record a healthy resting state. Turn on the simulated demand and leave the permissive healthy. Predict the command before advancing or observing the model. Then identify when feedback appears relative to the command. If the display updates too quickly to distinguish events, record that observation rather than inventing a delay.
Repeat with the permissive removed. A well-defined rung may still show demand, while the command stays off. This case is upstream of the output. In a separate paper case, set demand, permissive and command true while feedback stays false. The first disagreement is now downstream of the command. Trace the virtual output mapping and the feedback path before deciding that the program is wrong.
Use a competing explanation
Suppose two students suggest a failed feedback path and a missing starter supply. Both explanations can give command on and feedback off. Ask what additional observation would distinguish them. If the modeled contactor changes state but its input indication remains false, the feedback mapping deserves attention. If the contactor never changes state, the output-to-actuator path is the next section to understand. The distinction is more useful than guessing a replacement part.
A timer that supervises feedback adds a time condition. Record whether the mismatch exists only during the ordinary transition or persists beyond the configured supervision period. Time-stamped observations are useful even if the exercise does not include a dedicated alarm instruction. A momentary difference during a scan should not automatically be reported as a persistent fault.
Hand the evidence to another learner
Give your partner the four tag definitions, the scan rows and the first disagreement. Ask them to decide which observation would support each hypothesis. Then change the mode from automatic to hand in the model and repeat. A different command source can lead to the same output, while feedback retains its original meaning.
In real equipment, forcing an output or bypassing a permissive can start machinery or defeat protection. Keep this exercise within the simulator. The transferable skill is tracing the command and feedback as separate evidence, with a specific point at which their expected relationship breaks down.
Frequently asked question
Does a true feedback bit prove liquid flow?
Its meaning depends on the connected device. A contactor auxiliary contact indicates contactor position. Flow needs an appropriate process measurement or independent proof.
Continue the exercise
Open the matching practice tool · Read the background guide · Course outline