Scale a 4–20 mA pressure signal when the range starts at 2 bar
Work through five pressure points, separate offset from span error and interpret a diagnostic current on a 2–10 bar range.
PlantFlow 3D team · Instrumentation
Why a correct midpoint can look surprising
A pressure transmitter is configured for 2 to 10 bar. A learner sees 12 mA and writes 5 bar because 5 is half of 10. Another learner writes 6 bar. Both have recognized a midpoint, but only the second has used the actual lower value. Halfway through an eight-bar span is four bar above its starting value. Write the two endpoint pairs before doing any arithmetic.
Build the conversion from the endpoints
The current span is 20 minus 4, or 16 mA. Subtract 4 from the observed current to find its distance above live zero. Divide by 16 to obtain the fraction of span, multiply by the pressure span of eight bar, then add the lower range of two bar. For 12 mA the fraction is 0.5 and the answer is 2 + 0.5 × 8 = 6 bar.
Use the same steps backwards. A process value of 8 bar lies six bar above the lower limit, or three quarters of span. Three quarters of 16 mA is 12 mA above live zero. The predicted signal is therefore 16 mA. Converting back to 8 bar identifies both the units and the reference point in the calculation.
Run a five-point check
Open the calculator, enter the range as 2 and 10, then try 4, 8, 12, 16 and 20 mA. Write the expected pressures before revealing each answer. The sequence is 2, 4, 6, 8 and 10 bar. Each four-milliamp increment corresponds to two bar in this particular range. Do not reuse that step size for a transmitter with a different span.
Now set the receiver range to 0–10 bar on a second worksheet, leaving the simulated transmitter unchanged. At 4 mA the receiver predicts zero instead of two. At 12 mA it predicts five instead of six. At 20 mA both scales predict ten. A good high endpoint can therefore hide an incorrect lower-range configuration. Testing just the upper limit would miss this error entirely.
Separate a displayed number from signal quality
A linear calculator can produce a number for a current outside the normal range. That arithmetic does not establish that the number represents process pressure. Record the raw current, the quality or diagnostic label, the configured measurement range and the device settings. A zero-pressure reading, a valid lower-range reading and a failed loop are three different statements.
If the indicated pressure is consistently wrong while the raw current follows all five expected points, look first at the interpretation of the current. If the raw current itself stops rising toward the upper end, a range-setting change alone cannot explain that observation. In a learning exercise the voltage budget and modeled circuit continuity provide two separate checks.
Write the result as an engineering note
A useful note reads “For PT-101 configured at 2–10 bar, a 12 mA simulated input represents 6 bar. The receiver showed 5 bar only when its lower range was changed to zero.” Include the unit and identify which value was entered and which was calculated. That sentence is enough for another student to reconstruct the case.
Repeat once with a negative lower limit, for example −10 to +30 units. At 12 mA the result should be +10 units. This second range checks whether the method generalizes beyond the first set of numbers. Keep real transmitter adjustments and field circuit changes within the equipment procedure and the authority of the responsible technician.
Frequently asked question
Does 4 mA always mean zero pressure?
It represents the configured lower-range value. In this example it means 2 bar. A different linear transmitter range produces a different engineering value at exactly the same current.