Compare a healthy holding circuit with an open seal-in branch. Use four virtual observations to separate a starting fault from a holding fault.

PlantFlow 3D team · Motor control

Open in simulator

Start with the symptom

A learner presses START in the virtual panel. KM1 picks up and the motor indication appears. The instant the learner releases START, both disappear. This timing is the most valuable clue in the exercise. The circuit has already demonstrated that it can energize the coil under one condition. The question is what path should supply the coil after that condition ends. A report that says only “motor will not run” throws away this distinction.

Read the two possible paths

On the DOL drawing, locate the START contact and the normally open KM1 auxiliary contact marked 13–14. They join the same pair of electrical nodes, forming parallel paths. The healthy STOP and overload contacts form part of the common path. With the coil off, the auxiliary contact is open. Pressing START supplies the coil through the pushbutton. The contactor changes state and closes its own auxiliary contact. Releasing START opens one branch while the other remains available.

A helpful drawing exercise is to cover the power circuit with a sheet of paper and trace only the control path. Draw a second copy with START released and the coil picked up. A student who draws the auxiliary open in both copies has found the misconception before making a single wiring change.

Run four observations in the simulator

First observe the healthy circuit at rest. Record START open, KM1 released, the auxiliary open and the motor off. Next press START and record what changes. Release START and verify that KM1 remains picked up. Finally press STOP and confirm the coil and motor both drop out. These four rows create a reference against which a changed project can be compared.

In a separate copy of the virtual project, interrupt only the auxiliary branch. Repeat the same four actions. The new case should resemble the healthy one while START is pressed and differ at the moment of release. If KM1 never energizes, inspect the last edit and check that the pushbutton branch and the common return still exist. The interrupted branch should affect holding, not initial pickup.

Interpret a second fault before making another edit

Suppose START makes no difference at all. An open STOP path, tripped overload contact or incomplete coil return would affect both starting and holding. By contrast, a motor that continues running when STOP is pressed suggests that the common interruption is missing or bypassed in the model. These are different fault classes. Naming the component that changed state is more informative than naming a likely failed part.

Keep the virtual change and the conclusion separate in the worksheet. “Removed one end of the holding branch” describes an edit. “The coil drops at START release because both parallel paths are then open” explains a mechanism. Another student can test that explanation without seeing your file.

Finish with a restart check

Restore the original branch. Repeat start, release and stop. After STOP is released again, the motor should stay at rest until a new start command occurs. Record this last observation because a circuit that holds correctly can still have an unintended restart path. Export the working project and keep the failed example with a different filename if the class will compare them later.

For a real panel, terminal markings and protective functions must be verified against the equipment drawings. Use this exercise to learn how to reason from state changes. A simulated pass cannot authorize energizing a panel or bypassing a protective contact.

Frequently asked question

Can I find this fault from the power drawing alone?

The power drawing explains how the motor is supplied. The change at START release is best explained by following the coil supply and the parallel holding branch.