Find a range error using two endpoints and a midpoint
A transmitter configured for 0 to 50 units produces 7.5 V on a linear 0–10 V output. The expected receiver value is 37.5 units. Select a second case with a nonzero lower value to separate gain and offset errors.
Try the exercise
Test zero, middle and full scale. If the endpoints both match but an intermediate point does not, reconsider the assumed linear relationship. If the low endpoint is wrong by the same amount everywhere, inspect the lower-range configuration first.
Common fault or interpretation error
Using the 4–20 mA live-zero formula for a 0–10 V input introduces a spurious offset. Choose the expression that matches the configured signal.
Give a partner the midpoint reading only and ask whether the receiver range is correct. One point cannot distinguish all combinations of offset and gain. Add the lower endpoint and then the upper endpoint to make the comparison more discriminating. Mark whether each quantity on the worksheet represents terminal voltage or engineering units.
Frequently asked question
Is zero volts alone proof of an open signal wire?
Zero is a valid process endpoint for a zero-based voltage signal. A disconnected input can also behave differently depending on the receiver. Use the configured input and an independent indication to distinguish cases.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
Formula and worked example
Value = LRV + V / 10 × (URV − LRV)
0 + 7.5 / 10 × (50 − 0)
37.5 (75 %)
What to understand
Both signals carry one measurement from a transmitter to a PLC or controller. 0–10 V sends it as a voltage; 4–20 mA sends it as a current, where 4 mA is 0 % and 20 mA is 100 % of the range.
The biggest difference is the live zero. With 4–20 mA a healthy signal is never below about 3.8 mA, so 0 mA means a broken wire or a failed instrument, and the PLC can raise a fault alarm (NAMUR NE 43). With 0–10 V a broken wire reads 0 V, which looks exactly like a real zero measurement, so the fault can go unnoticed.
A current is the same everywhere in a series loop, so cable resistance and induced noise affect a 4–20 mA signal much less. That is why it is the standard for field instruments over long cables. 0–10 V is simple and cheap, and is common for short runs inside a panel, for example a speed reference to a VFD or a signal from an HVAC sensor.
For both, the value is linear: value = LRV + fraction × (URV − LRV), where the fraction is (mA − 4) / 16 for current and V / 10 for voltage. A 0–10 bar transmitter reading 12 mA or 5 V both mean 5 bar.
Open PLC & Process. Set the PT-101 fault to “Signal wire broken” (0–10 V) and the LT-101 fault to “Open loop” (4–20 mA), and compare the alarms.