Edit a schematic without changing the identity of its nodes
Pick a pushbutton and a coil on the DOL sheet. Mark which conductors actually share a terminal and which merely cross on the page. A tidy drawing is useful only when the underlying connections still match the intended circuit.
Try the exercise
Make one wire edit, observe the connection list, undo it and compare the endpoints with the baseline. Switch to the 3D view with the same project and return. The comparison should use component and terminal identifiers rather than screen coordinates.
Common fault or interpretation error
A wire drawn close to a terminal may still be unconnected. Confirm the registered connection before describing the circuit as complete.
Frequently asked question
Why can two drawings look different but behave identically?
Moving a symbol changes its position. A connection changes only when its endpoints or junctions change. A circuit can keep the same electrical structure even when the drawing is arranged for easier reading.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
A motor control drawing almost always shows two separate circuits. The power circuit carries the motor current from the supply through the breaker, the contactor main contacts and the overload relay to the motor. The control circuit is a low-power circuit, usually 230 V AC or 24 V DC, that decides when the contactor coil is energised.
Read the power circuit first to understand what the machine does, then read the control circuit to understand when it does it. In PlantFlow 3D the power circuit is on the left of the 2D diagram and the control circuit on the right.
IEC 81346 letter codes tell you what each device is: Q or QF for a breaker, KM for a power contactor, KA for a control relay, KT for a timer, F for protection such as an overload relay or MCB, S for push buttons and switches, H for pilot lamps, M for motors and T for transformers.
Terminal numbers follow a pattern. Main contacts are 1-2, 3-4 and 5-6. Auxiliary contacts ending in 3-4 are normally open (13-14, 43-44); those ending in 1-2 are normally closed (21-22, 31-32). Coils are A1-A2. On an overload relay 95-96 is the normally closed trip contact and 97-98 the normally open alarm contact.
Every contact is drawn in its de-energised, unpressed state. A normally open START button is drawn open; a normally closed STOP button is drawn closed. When you read a schematic, ask “what changes when this coil is energised?” and mentally flip every contact belonging to that device.
Start at the control supply L, follow the line through each contact and stop at the coil, then continue from A2 back to N. If any contact in the path is open, the coil is off. This is exactly how a technician fault-finds with a voltmeter: measure from N to each point along the path until the voltage disappears.
PlantFlow 3D draws live current in colour on the diagram, so you can see the path change when you press a button.