Use the ice point to separate a sensor curve from lead resistance
An ideal Pt100 has a nominal resistance of 100 ohms at 0 degrees Celsius. Near 100 degrees Celsius the standard 0.00385 characteristic gives approximately 138.5 ohms. Use these two checks to identify the sensor type and the scale of a result.
Try the exercise
Compare the calculated resistance at two nearby temperatures. Then consider a hypothetical two-wire circuit with extra series resistance. Predict whether interpreting that resistance as entirely sensor resistance makes the inferred temperature higher or lower.
Common fault or interpretation error
Using a constant slope over a large range loses the curvature of the characteristic. A resistance-to-temperature conversion also does not automatically compensate for field lead resistance.
Frequently asked question
Can a Pt100 reading be interpreted with a Pt1000 input setting?
The two sensors have different nominal resistances at zero degrees. Selecting the wrong type changes the interpretation fundamentally. Verify the receiver configuration before attributing an implausible result to temperature.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
Formula and worked example
Pt100 (IEC 60751): R = 100 × (1 + A·T + B·T²) A = 3.9083×10⁻³, B = −5.775×10⁻⁷
100 °C = 100 °C = 212 °F = 373.15 K
R(100 °C) = 138.51 Ω · T(138.51 Ω) = 100.01 °C
What to understand
A current loop sends the same current through every part of a series circuit, so long cables and connection resistance do not change the reading. The receiver measures the current, usually as the voltage across a known resistor such as 250 Ω, which turns 4–20 mA into 1–5 V.
The zero point is 4 mA, not 0 mA. This "live zero" means a broken wire (0 mA) can be told apart from a real minimum value.
Converting a current to a process value is a straight line: value = LRV + (I − 4) / 16 × (URV − LRV). For a level transmitter ranged 0–5 m, 12 mA is the middle: 2.5 m. The reverse is I = 4 + 16 × (value − LRV) / (URV − LRV).
A 2-wire transmitter takes its own power from the loop. A 24 V DC supply drives current through the transmitter and the input resistor; the transmitter regulates that current. The voltage left at the transmitter at 20 mA must stay above its minimum operating voltage from the data sheet, after subtracting the drop across the input and the cable.
Example: 24 V supply, 250 Ω input and 20 Ω of cable at 20 mA leaves 24 − 0.02 × 270 = 18.6 V at the transmitter.
Many transmitters follow the NAMUR NE 43 recommendation: currents at or below about 3.6 mA or at or above about 21 mA indicate a device fault rather than a measurement. A PLC can use those limits to raise a "transmitter fault" alarm and move the control to a safe action, as the pump station example in PlantFlow 3D does.
Open PLC & Process, then set the LT-101 fault to "open loop". Watch the PLC detect the fault and switch to the backup level switch. Use Tools → 4–20 mA to practise conversions.
Continue learning
4–20 mA current loops for beginners
Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.