Forward / reverse starter

Compare phase reversal and electrical interlocking in a reversing starter.

Open the example below. Change one item at a time, observe the result, then use the explanation to check your understanding.

Open in simulator

Interactive workspace
How to use this tool

Loading the tool…

Explain why reverse is refused while forward is active

Label the two commands independently. Exchanging two phases changes phase sequence in the power drawing. The directional decision belongs in the control drawing. Look for a normally closed auxiliary contact from the opposite contactor in each coil path.

Try the exercise

Run the forward example. Predict the response to a reverse request before pressing it. Stop, confirm that the existing contactor has released, and then request reverse. Compare coil indication and motor direction after each action. Observe both directions from the same reference viewpoint.

Common fault or interpretation error

If one direction never starts, compare the common stop chain with the direction-specific command and interlock. A working forward path does not prove that the reverse coil has a complete return.

Give a partner a small four-row truth table with the states rest, forward, rest again and reverse. In each row include the requested direction, the forward coil, the reverse coil and the reported motion. Then ask which row would be impossible with the intended interlock. Both coil indicators active together is a contradiction worth investigating even if the motor animation appears to choose one direction. Conversely, both coils off between commands is an ordinary state. That difference helps a student explain why a recorded pause alone is insufficient evidence for an interlock fault.

Frequently asked question

Can two independent start buttons provide interlocking by themselves?

Separate buttons identify the requested direction. They do not establish mutual exclusion. Opposite auxiliary contacts, suitable mechanical interlocking and the design requirements determine how contradictory commands are handled.

A simple practice routine

  1. Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
  2. Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
  3. Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.

Understand the example

A three-phase induction motor turns in the direction of its rotating magnetic field. Swapping any two of the three supply phases reverses that field and so reverses the motor. A forward–reverse starter does this with two contactors: KM1 connects L1-L2-L3 in order, KM2 connects them with two phases exchanged.

If both contactors closed at the same moment, two phases would be connected directly to each other through the main contacts: a short circuit. That is why every reversing starter is interlocked.

The electrical interlock puts a normally-closed auxiliary contact of KM2 in the coil circuit of KM1, and a normally-closed contact of KM1 in the coil circuit of KM2. Whichever contactor is in, the other cannot be energised.

Many circuits also use double push buttons: the FORWARD button has a normally-closed contact in the REVERSE circuit and vice versa. Pressing one direction first breaks the other. Mechanical interlocks between the contactors give a third independent layer.

Reversing a large load directly from full speed puts heavy mechanical and electrical stress on the machine. Many applications require the operator to press STOP and wait before reversing.

If the motor hums but does not turn in one direction, check the reversing contactor's main contacts. If one direction will not start at all, check the interlock contact of the opposite contactor and its wiring.

Load the Forward–Reverse starter, run it in both directions, then try removing an interlock wire in the 2D diagram. The inspector flags the danger before you simulate it.

Continue learning

Forward–reverse motor control and interlocks

Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.