Find the first point shared by two stopped feeders
Give each feeder its own identifier. Follow the common incomer, shared bus and individual starter branches. Record which device is upstream of both motors and which devices can affect only one branch. This is the useful distinction when two faults look similar.
Try the exercise
Observe one running feeder. Open a branch control in the model, then compare the consequences with a common interruption. Make a two-column list of devices eliminated by the healthy feeder and devices that remain plausible for the failed one.
Common fault or interpretation error
Copying one feeder tag onto another can create a convincing but false fault report. Include the feeder reference and the exact device tag in the observation.
For the handover note, identify the source of each indication. A feeder lamp supplied from control power can remain available when the associated power path is interrupted. Record whether the symptom concerns the common bus or one outgoing unit.
Frequently asked question
Can a common supply fault be eliminated because a pilot lamp is lit?
Only if the lamp is known to be fed from the point relevant to the diagnosis. A control lamp can have a separate supply. Trace its source before using the indication as evidence.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
A Motor Control Centre is an assembly of motor starters fed from one common busbar. Each motor has its own feeder (often called a bucket or drawer) with a breaker, a contactor, an overload relay and its own control circuit. Plants use MCCs so that pumps, fans and conveyors can be started, stopped and isolated from one place.
A typical DOL feeder contains: a motor-protection breaker or MCCB for short-circuit protection and isolation; a contactor for switching; a thermal or electronic overload relay set to the motor full-load current; START and STOP buttons or a PLC output; and a running lamp. Larger motors use star-delta, soft starter or VFD feeders instead.
Every feeder must work independently: pressing STOP on feeder 1 must not stop feeder 2. Only a common emergency stop, or the loss of the incoming supply, stops all of them.
MCCs usually make their 230 V or 110 V control voltage with a control transformer connected between two phases of the busbar. The secondary is separate from the supply, so a fault in the control wiring stays in a small, fused circuit. If the primary loses a phase, the control voltage disappears and all contactors drop out, which is the safe direction to fail.
An MCC in a plant is often fed from its own distribution transformer, for example 11 kV to 400 V Dyn11. The primary current is much smaller than the secondary current: I1 ≈ I2 × V2 / V1. For 40 A on the 400 V side, the 11 kV side carries about 1.5 A.
Load “MCC with transformer (2 feeders)”. Start both feeders, then press Stop 1 and see that feeder 2 keeps running. Press the E-stop to stop both.