Trace one final circuit back to its own protective device
Select a single outgoing load and follow its line, neutral and protective paths on the model. Use the device labels and circuit references as evidence. On a nominal 230/400 V system, line-to-neutral and line-to-line references represent different voltages.
Try the exercise
Identify which loads lose their supply when one modeled branch opens. Compare with opening a common upstream device. Record both affected and unaffected loads so the exercise distinguishes a branch interruption from a board-wide event.
Common fault or interpretation error
A return assigned to the wrong protective group can be hard to detect from the line conductor alone. Follow the complete circuit in the drawing.
Frequently asked question
Can a board drawing prove a protective device will disconnect in time?
A drawing shows intended topology. Verification also requires the actual protective device characteristics, circuit parameters, applicable rules and installation test results. A simulator cannot certify disconnection time.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
A TN-S supply brings three phases L1, L2 and L3, a neutral N and a separate protective earth PE. Between two phases there are 400 V; between a phase and neutral there are 230 V. Final circuits such as lighting, sockets and water heaters are connected from one phase to neutral.
A load connected by mistake between two phases receives 400 V and is destroyed, so the wiring and labelling of each circuit matter.
Single-phase circuits are spread over L1, L2 and L3 so that each phase carries about the same current. When the loads are balanced, the three neutral currents cancel because they are 120° apart. When one phase carries more, the difference flows back in the neutral. Good balance keeps the neutral current, the voltage drop and the supply transformer loading low.
Each final circuit has a miniature circuit breaker sized for its cable. On overload the thermal release trips after a delay that gets shorter as the current rises; on a short circuit the magnetic release trips at once. The B curve trips magnetically at 3–5 times its rating, C at 5–10 times and D at 10–20 times.
With good selectivity a fault on one circuit trips only that circuit’s MCB, and the rest of the board stays on.
A residual current device compares the current going out on the lines with the current coming back on the neutral. If the difference, which is current leaking to earth, reaches its rated residual current IΔn, it trips. A 30 mA RCD gives additional protection against electric shock for socket and lighting circuits.
An RCD also trips if a neutral is connected to earth after the RCD, because the return current then bypasses it. Press the test button regularly. If an RCD trips at every reset, switch off the final circuits one by one to find the faulty one, then test its insulation.
Choose “Distribution board” in the simulator. Read the phase and neutral currents, switch one MCB off and watch the neutral current rise, then press the RCD test button and simulate an earth fault.
Continue learning
Three-phase distribution boards, MCBs and RCDs
Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.