Project cable check — How to calculate a three-phase motor's full-load current, why the nameplate value wins, and how it is used for overload and cable checks.

Open the example below. Change one item at a time, observe the result, then use the explanation to check your understanding.

Open in simulator

Interactive workspace
How to use this tool

Loading the tool…

Test a candidate cable against the circuit assumptions

Write down the design current, selected protective-device rating and installed cable capacity as three independent quantities. The capacity comes from an identified cable type and installation method. The model lets you compare a candidate with the circuit assumptions.

Try the exercise

Use a candidate whose corrected capacity is higher than the selected device rating. Lower its capacity in a second case and note the first inequality that stops holding. Record which assumption changed, such as grouping or ambient conditions.

Common fault or interpretation error

Confusing a correction factor with a percentage can create an unrealistic result. Enter a dimensionless factor in the convention requested by the tool.

On the worksheet show the failed comparison explicitly. For example, a corrected capacity below the selected protective rating leaves the candidate unsuitable for that stated comparison even if the normal load current fits. Keep the thermal check separate from the voltage-drop result and identify which additional checks remain outside the classroom model.

Frequently asked question

Why can an unchanged conductor pass one comparison and fail another?

Installation conditions affect the permitted current. A candidate cross-section alone cannot establish ampacity. The thermal environment, insulation and installation method all influence a real selection.

A simple practice routine

  1. Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
  2. Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
  3. Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.

Understand the example

For a three-phase motor the input power is P_in = P_out / η, and the line current is I = P_out / (√3 × V × pf × η). Here P_out is the rated shaft power in watts, V the line voltage, pf the power factor and η the efficiency.

Example: 7.5 kW, 400 V, pf 0.85, η 0.90 gives I = 7500 / (1.732 × 400 × 0.85 × 0.90) ≈ 14.2 A. PlantFlow 3D shows this as a calculated estimate.

Real motors differ: efficiency and power factor change with size, speed and design, and the manufacturer has measured the actual rated current. Whenever the nameplate current is known, use it for the overload setting and for checking cables and switchgear. The simulator marks calculated values as estimates and lets you enter the nameplate value.

The rated current sets the thermal overload relay, guides the contactor size (utilisation category AC-3 for squirrel-cage motors), and is the design current for the cable check together with the cable length, installation method and voltage drop limit.

Starting current is several times the rated current for a direct-on-line start. The exact ratio comes from the motor data sheet. In the simulator it is a teaching assumption that you can change.

Cable current ratings depend on conductor size, insulation, installation method, ambient temperature and grouping. These values come from the cable manufacturer or the standard that applies to your project. PlantFlow 3D does not include those tables: you enter the verified rating and correction factors, and it checks the coordination and voltage drop.

Open Tools → Cable check, link it to motor M1 and enter your cable data. Change the motor power in the Data tab and see the load schedule update automatically.

Continue learning

Motor full-load current and overload settings

Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.