Home / Calculators / Cable ampacity check

Calculators

Cable ampacity check

Check a chosen cable rating against load current, breaker rating and correction factors.

Change a number below. The formula, working and result update together.

Open tool

Check a stated cable ampacity after derating

Try a design current of 14 A, a 16 A protective device, a tabulated cable rating of 27 A and a correction factor of 0.80. The corrected capacity is 21.6 A. Compare the design current, device rating and corrected capacity in that order.

Try the exercise

Repeat with a factor of 0.55. The corrected capacity is then 14.85 A, below the selected 16 A rating. Identify which comparison failed and why the original table value cannot be used unchanged for this case.

Common fault or interpretation error

Entering an already derated rating and then applying the same factor again double-counts the reduction. State whether your input is tabulated or corrected.

Frequently asked question

Which conductor cross-section does the result select?

The tool evaluates the tabulated candidate you supply. Obtain the cross-section and tabulated rating from the applicable cable table for the actual conditions. It does not select a universal millimetre-squared size.

A simple practice routine

  1. Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
  2. Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
  3. Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.

Understand the example

Formula and worked example

Ib ≤ In; It ≥ In / (Ca × Cg × Ci)

14.2 ≤ 16; It ≥ 16 / 0.8 = 20 A

✔ OK: the cable rating covers the protective device after correction.

PlantFlow never invents cable ratings: take It and the correction factors from the standard that applies to you or from the cable manufacturer.

What to understand

For a three-phase motor the input power is P_in = P_out / η, and the line current is I = P_out / (√3 × V × pf × η). Here P_out is the rated shaft power in watts, V the line voltage, pf the power factor and η the efficiency.

Example: 7.5 kW, 400 V, pf 0.85, η 0.90 gives I = 7500 / (1.732 × 400 × 0.85 × 0.90) ≈ 14.2 A. PlantFlow 3D shows this as a calculated estimate.

Real motors differ: efficiency and power factor change with size, speed and design, and the manufacturer has measured the actual rated current. Whenever the nameplate current is known, use it for the overload setting and for checking cables and switchgear. The simulator marks calculated values as estimates and lets you enter the nameplate value.

The rated current sets the thermal overload relay, guides the contactor size (utilisation category AC-3 for squirrel-cage motors), and is the design current for the cable check together with the cable length, installation method and voltage drop limit.

Starting current is several times the rated current for a direct-on-line start. The exact ratio comes from the motor data sheet. In the simulator it is a teaching assumption that you can change.

Cable current ratings depend on conductor size, insulation, installation method, ambient temperature and grouping. These values come from the cable manufacturer or the standard that applies to your project. PlantFlow 3D does not include those tables: you enter the verified rating and correction factors, and it checks the coordination and voltage drop.

Open Tools → Cable check, link it to motor M1 and enter your cable data. Change the motor power in the Data tab and see the load schedule update automatically.

Continue learning

Motor full-load current and overload settings

Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.