Estimate the effect of doubling a feeder length
Choose a balanced example and record the conductor material, cross-section, design current and one-way route length. Compare two lengths while keeping every other input fixed. In this simplified resistive model twice the length should produce twice the calculated drop.
Try the exercise
Write down volts and percent for the baseline. Double the route length, restore it, and then double the conductor area. Verify that the two changes act in opposite directions. Read the displayed formula to see how the model treats the phase arrangement.
Common fault or interpretation error
Entering the return length twice in a field that expects one-way length changes the modeled path. State the length convention in the calculation note.
Frequently asked question
Does a small calculated drop prove the conductor is large enough?
Voltage drop is one check. Current capacity, protective coordination, fault withstand and the adopted installation requirements are separate. The model also simplifies conductor temperature and impedance.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
Formula and worked example
ΔV = √3 × I × (ρ × L / S) × cos φ
ΔV = √3 × 14.2 × (0.0225 × 60 / 4) × 0.85 = 7.056 V
7.056 V = 1.76 %
Resistive voltage drop at about 70 °C; reactance is neglected, so large cables read slightly low.
What to understand
For a three-phase motor the input power is P_in = P_out / η, and the line current is I = P_out / (√3 × V × pf × η). Here P_out is the rated shaft power in watts, V the line voltage, pf the power factor and η the efficiency.
Example: 7.5 kW, 400 V, pf 0.85, η 0.90 gives I = 7500 / (1.732 × 400 × 0.85 × 0.90) ≈ 14.2 A. PlantFlow 3D shows this as a calculated estimate.
Real motors differ: efficiency and power factor change with size, speed and design, and the manufacturer has measured the actual rated current. Whenever the nameplate current is known, use it for the overload setting and for checking cables and switchgear. The simulator marks calculated values as estimates and lets you enter the nameplate value.
The rated current sets the thermal overload relay, guides the contactor size (utilisation category AC-3 for squirrel-cage motors), and is the design current for the cable check together with the cable length, installation method and voltage drop limit.
Starting current is several times the rated current for a direct-on-line start. The exact ratio comes from the motor data sheet. In the simulator it is a teaching assumption that you can change.
Cable current ratings depend on conductor size, insulation, installation method, ambient temperature and grouping. These values come from the cable manufacturer or the standard that applies to your project. PlantFlow 3D does not include those tables: you enter the verified rating and correction factors, and it checks the coordination and voltage drop.
Open Tools → Cable check, link it to motor M1 and enter your cable data. Change the motor power in the Data tab and see the load schedule update automatically.
Continue learning
Motor full-load current and overload settings
Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.