Motor current calculator

Estimate single-phase or three-phase current from power, voltage, power factor and efficiency.

Change a number below. The formula, working and result update together.

Open tool

Estimate the full-load current of a 7.5 kW motor

Use mechanical output power of 7.5 kW, a three-phase line voltage of 400 V, a power factor of 0.85 and efficiency of 90 percent. The estimate is about 14.15 A. A common error is treating the shaft rating as electrical input and omitting efficiency.

Try the exercise

Enter the baseline, then reduce power factor while keeping voltage and efficiency fixed. Predict the current direction before reading the result. Compare the answer with the corresponding nameplate example and record the assumptions separately from a measured current.

Common fault or interpretation error

Entering 0.9 in a box labeled efficiency percent means 0.9 percent. Enter 90 for this example. The power factor box uses a fraction such as 0.85.

Frequently asked question

Why use 400 V rather than 230 V in this example?

The three-phase expression already includes the square root of three and expects line-to-line voltage. Substituting line-to-neutral voltage in the same expression gives an inappropriate result for the stated system.

A simple practice routine

  1. Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
  2. Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
  3. Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.

Understand the example

Formula and worked example

I = P / (√3 × V × cos φ × η)

I = 7,500 / (√3 × 400 × 0.85 × 0.9)

14.15 A

Use the nameplate full-load current for settings. This estimate is for planning only.

What to understand

For a three-phase motor the input power is P_in = P_out / η, and the line current is I = P_out / (√3 × V × pf × η). Here P_out is the rated shaft power in watts, V the line voltage, pf the power factor and η the efficiency.

Example: 7.5 kW, 400 V, pf 0.85, η 0.90 gives I = 7500 / (1.732 × 400 × 0.85 × 0.90) ≈ 14.2 A. PlantFlow 3D shows this as a calculated estimate.

Real motors differ: efficiency and power factor change with size, speed and design, and the manufacturer has measured the actual rated current. Whenever the nameplate current is known, use it for the overload setting and for checking cables and switchgear. The simulator marks calculated values as estimates and lets you enter the nameplate value.

The rated current sets the thermal overload relay, guides the contactor size (utilisation category AC-3 for squirrel-cage motors), and is the design current for the cable check together with the cable length, installation method and voltage drop limit.

Starting current is several times the rated current for a direct-on-line start. The exact ratio comes from the motor data sheet. In the simulator it is a teaching assumption that you can change.

Cable current ratings depend on conductor size, insulation, installation method, ambient temperature and grouping. These values come from the cable manufacturer or the standard that applies to your project. PlantFlow 3D does not include those tables: you enter the verified rating and correction factors, and it checks the coordination and voltage drop.

Open Tools → Cable check, link it to motor M1 and enter your cable data. Change the motor power in the Data tab and see the load schedule update automatically.

Continue learning

Motor full-load current and overload settings

Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.