A balanced three-phase load draws 10 A from a 400 V line-to-line supply. Its apparent power is approximately 6.93 kVA. At a power factor of 0.8, its real electrical input is about 5.54 kW. Mechanical output would require separate efficiency information.
Try the exercise
Enter the example and record both units. Repeat at the same current and voltage with a different power factor. Apparent power remains tied to voltage and current, while the real component changes. Explain the result without treating the displayed values as interchangeable.
Common fault or interpretation error
Multiplying by three and also using the line-voltage square-root-of-three formula counts the phase relationship twice.
On the worksheet place energy in a separate column. A constant 5.54 kW real load running for two hours would use about 11.08 kWh under the stated steady assumptions.
Frequently asked question
Can kVA and kW have the same numerical value?
They can when the overall power factor is one. For lower power factor a given apparent power corresponds to less real power. The distinction matters when comparing a load with a transformer or generator rating.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
Formula and worked example
S = √3 × V × I; P = S × cos φ; Q = √(S² − P²)
S = √3 × 400 × 14.2 = 9.838 kVA
9.838 kVA · 8.362 kW · 5.183 kVAR
What to understand
A motor takes real power (kW), which does the work, and reactive power (kvar), which builds its magnetic field and flows back and forth without doing work. The supply must carry both, so the current is larger than the real power alone would need. Power factor is the ratio of real power to apparent power (kVA): 1.0 is ideal, and a lightly loaded motor may be well below 0.8.
A capacitor takes reactive power of the opposite sign. Placed near the load, a capacitor bank supplies the motor's reactive power locally, so less of it flows from the supply. The real power stays the same, but the apparent power and the line current fall, which reduces cable losses and can avoid utility penalties for low power factor.
Example: a motor taking 8.3 kW at power factor 0.85 also takes about 5.2 kvar. Adding 4 kvar of capacitors leaves about 1.2 kvar, and the power factor rises to about 0.99.
Loads change, so banks are split into steps switched by contactors. A power factor relay reads the current and voltage and switches steps in when the power factor is below the target, and out again when the load falls. Too much capacitance makes the power factor leading, which is also undesirable.
Capacitors store charge. Each step needs time to discharge, normally through built-in resistors, before it may be switched in again, and before anyone touches the terminals. Use the discharge time and ratings from the capacitor data sheet.
Choose “Power factor correction” in the simulator, start the motor and watch the power meter as the relay switches in the two capacitor steps. Then stop the motor.
Continue learning
Power factor and capacitor banks
Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.