Keep real power fixed while changing reactive demand
Start with a simple worked load of 8 kW at power factor 0.8. Its apparent power is 10 kVA. Correction supplies part of the reactive demand locally, reducing the apparent power required from the source when real load and voltage stay comparable.
Try the exercise
Sketch the active and reactive components. Compare a target power factor of 0.95 with the original value. Divide 8 by 0.95 to estimate 8.42 kVA after correction. Explain why this comparison alone cannot select a capacitor bank or its switching steps.
Common fault or interpretation error
Using the difference in kVA as if it were a kvar rating mixes two different quantities. Use the reactive components of the power triangles.
Work out the reactive requirement before selecting a training case. At 8 kW and 0.8 power factor the initial reactive component is 6 kvar. At a target power factor of 0.95 it is about 2.63 kvar. The difference is roughly 3.37 kvar at that operating point. Record the two conditions and avoid treating this classroom difference as a recommendation for an installed bank.
Frequently asked question
Can improved power factor be counted as the same percentage saving in kWh?
Real energy depends on real power and duration. Changes in upstream losses or tariffs may matter, but the ratio change alone cannot establish a matching reduction in metered energy.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
A motor takes real power (kW), which does the work, and reactive power (kvar), which builds its magnetic field and flows back and forth without doing work. The supply must carry both, so the current is larger than the real power alone would need. Power factor is the ratio of real power to apparent power (kVA): 1.0 is ideal, and a lightly loaded motor may be well below 0.8.
A capacitor takes reactive power of the opposite sign. Placed near the load, a capacitor bank supplies the motor's reactive power locally, so less of it flows from the supply. The real power stays the same, but the apparent power and the line current fall, which reduces cable losses and can avoid utility penalties for low power factor.
Example: a motor taking 8.3 kW at power factor 0.85 also takes about 5.2 kvar. Adding 4 kvar of capacitors leaves about 1.2 kvar, and the power factor rises to about 0.99.
Loads change, so banks are split into steps switched by contactors. A power factor relay reads the current and voltage and switches steps in when the power factor is below the target, and out again when the load falls. Too much capacitance makes the power factor leading, which is also undesirable.
Capacitors store charge. Each step needs time to discharge, normally through built-in resistors, before it may be switched in again, and before anyone touches the terminals. Use the discharge time and ratings from the capacitor data sheet.
Choose “Power factor correction” in the simulator, start the motor and watch the power meter as the relay switches in the two capacitor steps. Then stop the motor.
Continue learning
Power factor and capacitor banks
Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.