Follow a run command without confusing it with the speed reference
A drive can have a valid run request and still receive a zero speed reference. Identify the supply side, the drive output and the control inputs in the drawing. Distinguish the command source from the reference source on your worksheet.
Try the exercise
Use the virtual start and stop controls and follow the displayed drive state. Compare a run demand at two available reference settings or calculate the two expected frequency ratios on paper. Document which observations the model displays and which would require an actual drive parameter list.
Common fault or interpretation error
An enabled keypad with a remote run command is a common source-selection misunderstanding. A valid terminal state has no effect when the configured command source is elsewhere.
Frequently asked question
Does half rated frequency always mean half shaft speed?
For a given pole count synchronous speed is proportional to frequency. Motor slip, the control method and load affect actual shaft speed. The simulated reference alone does not establish measured speed.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
A variable frequency drive feeds an induction motor from a supply whose frequency and voltage it can change. The motor speed follows the frequency: at 25 Hz a 4-pole motor turns at roughly half its 50 Hz speed. The drive first rectifies the three-phase supply to DC, smooths it in a DC link, then switches that DC with transistors to build a new three-phase output.
Because the drive raises the frequency gradually, from a few hertz up to the set point, the motor accelerates smoothly. The current stays close to the motor rating instead of the large inrush of a direct-on-line start.
To keep the magnetic flux in the motor roughly constant, a basic drive keeps the voltage in proportion to the frequency (V/f control). At half frequency the output voltage is about half, which is why a multimeter on the drive output reads less than 400 V while the motor runs slowly.
Most drives have their own 24 V DC supply for digital inputs. A typical three-wire scheme uses a normally-closed stop button on one input (the drive runs only while it is closed), a start-forward button and a start-reverse button. Never connect 230 V control voltage to these inputs: it destroys them.
The acceleration and deceleration times, the speed set point and the motor data are parameters in the drive. Reversing does not need a second contactor: the drive simply changes the order of its output phases.
Mains voltage must never reach the drive output terminals U, V and W, for example through a wrongly wired bypass contactor. Contactors between the drive and the motor should only switch when the drive is stopped. If a supply phase is missing, the drive stops and reports an undervoltage or phase-loss fault.
Choose “VFD drive” in the simulator, start forward, change the speed set point to 25 Hz and press reverse. Watch the frequency, current and output voltage.
Continue learning
Variable frequency drives (VFD) explained
Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.