Use a game result to choose the next practice task
Pick one electrical or instrumentation challenge. Before attempting it, read the actual success condition. A level about a switched lamp tests a different idea from a motor holding circuit even though both contain a load and a control device.
Try the exercise
Try the challenge, record the first mismatch, and compare the feedback with the corresponding circuit guide. Repeat after changing only the suspected connection. Keep the final score with a one-sentence explanation of why the final attempt passed.
Common fault or interpretation error
Trying changes at random can eventually pass a small puzzle. Reconstruct the successful path afterwards so another learner can reproduce the reasoning.
Ask a partner to explain a second valid solution, if the exercise permits one, and to identify a connection that looks plausible but violates the stated goal.
Frequently asked question
What does a completed level tell a teacher?
It establishes that the learner met the checks defined for that exercise. Ask them to predict a changed case to see whether they can transfer the principle beyond the practiced layout.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
Ask exactly what happens. Does nothing happen when START is pressed? Does the contactor pull in but the motor hums? Does the motor start and stop after some minutes? Each symptom points to a different part: control circuit, power circuit or protection.
Then look before you measure: a tripped breaker, an overload showing “tripped”, burnt marks, loose wires and indicator lamps tell you a lot in seconds.
If the contactor does not pull in, follow the control voltage from the supply to coil terminal A1, measuring against N. The voltage is lost at the first open element: a tripped overload (95-96), a pressed or faulty STOP button, a broken wire, or a START contact that does not close. If A1 has 230 V, measure across A1-A2: 230 V there with no pull-in means an open coil or a missing neutral on A2.
For a motor that hums but does not turn, measure the three phases at the contactor output and at the motor terminals: a missing phase gives single-phasing, which also trips the overload.
When you have found the suspect part, isolate, lock off and prove dead. Confirm with continuity or resistance, replace or repair, then tighten terminals and check the wire numbers against the drawing.
Before handing back, test the circuit: START, STOP, the overload TEST button, the emergency stop and any interlocks. Write down what you found and changed.
Open or loose control wire, overload tripped by a lost phase, STOP button contact worn, contactor coil open, wrong coil voltage, seal-in contact 13-14 not wired (motor runs only while START is held), and a motor connected in star instead of delta.
Open the 🔧 Troubleshoot tool on the Wiring tab. Pick the item that does not work and follow the voltage step by step until it is lost. The practical lessons hide real faults for you to find.
Continue learning
Troubleshooting a motor control circuit step by step
Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.