Use the first circuit lesson to establish a baseline
Choose a simple circuit journey and read its learning objective. Before pressing a control, identify what would count as success. A student who can explain why the load changes state has learned more than one who merely follows a sequence of taps.
Try the exercise
Work through one stage and record the expected state. After an incorrect action, read the hint and explain which assumption it corrects. Return to a previous observation and connect it to the next stage. Save or export an example you want to keep.
Common fault or interpretation error
Rushing through hints may complete the screen without identifying the circuit path. Ask for the device tag or terminal pair that supports the answer.
Frequently asked question
Should a class repeat the whole lesson after one wrong answer?
A targeted repeat of the stage that exposed the misconception is usually more informative. Ask the student to state both the predicted result and the reason for the revised prediction.
A simple practice routine
- Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
- Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
- Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.
Understand the example
A direct-on-line (DOL) starter connects a three-phase motor straight to the full supply voltage. It is the simplest and most common way to start small and medium motors: one contactor closes, all three phases reach the motor at once and the motor accelerates to full speed in a few seconds.
Because the motor gets full voltage while it is still stationary, it draws a large starting current, typically several times its full-load current, until it comes up to speed. That is why DOL is used where the supply can take that inrush and the driven machine can take a sudden start.
The power circuit carries the motor current. It normally has three parts in series: a circuit breaker or fused switch (short-circuit protection and isolation), the main contactor KM1 (switching), and a thermal overload relay (protection against too much current for too long).
In PlantFlow 3D these are QF1, KM1 and F1. Follow L1, L2 and L3 from the supply through QF1, through the main contacts 1-2, 3-4 and 5-6 of KM1, through the overload heaters and on to the motor terminals U1, V1 and W1.
The control circuit decides when the contactor coil A1-A2 is energised. Pressing START closes a normally-open push button, current flows through the normally-closed STOP button and the overload contact 95-96 to the coil, and KM1 pulls in.
When you release START the motor must keep running, so an auxiliary normally-open contact of KM1 (13-14) is wired in parallel with the START button. This "seal-in" or "hold-in" contact keeps the coil fed. Pressing STOP, or the overload contact opening, breaks the circuit; the coil drops out and the seal-in contact opens too, so the motor will not restart on its own.
A short circuit is cleared by the breaker in a fraction of a second, but a motor that is slightly overloaded or has lost one phase draws only a moderately higher current. That will not trip the breaker, yet it overheats the windings over minutes. The thermal overload relay models that heating and opens its 95-96 contact before the insulation is damaged.
Continue learning