ATS mains / generator

Follow mains failure, generator starting and supply transfer.

Open the example below. Change one item at a time, observe the result, then use the explanation to check your understanding.

Open in simulator

Interactive workspace
How to use this tool

Loading the tool…

Record the gap between losing one source and accepting another

Name the two virtual sources A and B. Keep a separate column for source availability and switch position. The presence of voltage on the alternate side does not by itself prove that the load has transferred to it.

Try the exercise

Observe a normal supply, simulate loss using the available controls, and follow the two switch positions through the transition. Record a transfer interval in which neither source feeds the load if the model uses open transition. Repeat for restoration of the normal source.

Common fault or interpretation error

A timer still counting may look like a failed transfer. Distinguish a pending condition from a command whose feedback never changes.

A transfer worksheet needs source availability, acceptance timer, switch command and confirmed position. For a classroom example mark the alternate supply healthy before it is accepted. Ask whether the switch is permitted to move at that instant. Next consider a commanded transfer with no corresponding position feedback. The first case describes waiting for a condition, while the second suggests a failed transition. At the end, trace the supplying source through to the load. A lamp wired on the incoming side can stay on even though its source is disconnected from the load.

Frequently asked question

Does a healthy generator indication mean that the load has been transferred?

It confirms only the modeled source condition. Transfer also depends on the controller decision, switching position and interlocks. Confirm the load-side path in the diagram before naming the supplying source.

A simple practice routine

  1. Identify the supply, the load and the control devices before changing the example. Read the terminal names and compare them with the linked guide.
  2. Make one change, then observe the effect. For a circuit, use the diagram and connection check; for a calculator, check the units and the formula.
  3. Return the example to its original condition and repeat the task. Save or export a project from its Project menu before leaving if you need a permanent copy.

Understand the example

Hospitals, fire pumps, data rooms and many factories have loads that must keep running when the mains fails. An automatic transfer switch watches the mains. When it fails, the ATS starts a standby generator and moves the load to it. When the mains returns, it moves the load back.

A typical open-transition sequence is: confirm the mains failure for a short time (to ignore brief dips), send the start signal to the generator, wait until the generator voltage is healthy, open the mains contactor, wait a short dead time, then close the generator contactor. On mains return it waits a return delay to be sure the mains is stable, transfers back the same way, and lets the generator run unloaded for a cool-down time before stopping it.

The mains and the generator are separate sources with different phase angles. Connecting them together would cause a huge current. The mains and generator contactors are therefore interlocked electrically (each coil circuit passes through a normally-closed auxiliary contact of the other) and often mechanically as well. Closed-transition transfer, where both are briefly connected, needs synchronising equipment and the approval of the supply authority.

An ATS should be tested regularly by simulating a mains failure, checking the start, transfer, return and cool-down times, and confirming that the essential load really runs on the generator.

Choose “ATS” in the simulator, press “simulate failure” and follow each step of the transfer in the status bar. Then try the troubleshooting challenges.

Continue learning

Automatic transfer switches (ATS) for standby generators

Learning model: follow equipment instructions and applicable local rules for real installations. A simulated check is not installation approval.